The numbers for common heaters
| Heater | 240 V single-phase (US/CA) | 230 V single-phase (EU/UK) | 400 V three-phase (EU) |
|---|---|---|---|
| 4.5 kW | 18.8 A → 25 A breaker | 19.6 A → 20–25 A | 6.5 A per phase → 3 × 10 A |
| 6 kW | 25 A → 35 A breaker | 26.1 A → 32 A | 8.7 A per phase → 3 × 10 A |
| 8 kW | 33.3 A → 45 A breaker | 34.8 A → 40 A | 11.5 A per phase → 3 × 13–16 A |
| 9 kW | 37.5 A → 50 A breaker | 39.1 A → 40 A | 13 A per phase → 3 × 13–16 A |
Current = power ÷ voltage (three-phase: power ÷ (√3 × 400 V)). In the US, electricians size a fixed heater's circuit as a continuous load at 125% of its current (NEC 424.4(B)), then round up to a standard breaker. The heater's own manual has the final word on breaker, cable and the controller's wiring.
What to tell your electrician
- Heater model, kW, voltage and phase, and the manual's breaker and cable table.
- Where the heater and the controller go, and the cable length from the panel.
- Whether your panel has room for a 2-pole 240 V breaker (US/CA) or a three-phase supply (EU).
- Heat-resistant cable inside the hot room, as the manual requires (often silicone-insulated).
We never give DIY wiring steps: sauna heaters are high-current, hot and in a damp room, and most countries require a licensed electrician and often a permit.